6 Table Output Function
6.4 Procedures for executing table output function
A
Common Items
B
FX
3U
-4AD
FX
3UC
-4AD
C
FX
3U
-4AD-ADP
D
FX
3G
-2AD-BD
E
FX
3U
-4DA
F
FX
3U
-4DA-ADP
G
FX
3G
-1DA-BD
H
FX
3U
-3A-ADP
I
FX
3U
-4AD-PT
-ADP
J
FX
3U
-4AD-PTW
-ADP
FX
3G
/FX
3U
/FX
3UC
PLC User's Manual - Analog Control Edition
FX3U-4DA (4-channel Analog Output)
4. Cautions regarding table output
When BFM #99 (data table transfer command) is not H0000, the table output function cannot be started.
When an error occurs during transfer of data table, start the table output after setting the correct data table.
While the table output completion flag BFM #89 is ON, output of a new table cannot be started.
The table output function is valid only while the PLC is in RUN mode.
While even a single channel is outputting data table (BFM #80 is not H0000), it is prohibited to change
BFM #0, #5, #9 to #17, #19, #20, #32 to #35, #38, #41 to 48, #50 to #54 and #60 to #63.
The pattern can be changed during output as shown below. (The change is invalid while the table output
completion flag BFM #89 is ON.)
5. Check the table output completion flag. (BFM #89, initial value: H0000)
The value in BFM #89 indicates whether the table output from each channel has been completed.
After data is output at the final point in the last cycle of a pattern, the table output completion flag is turned on.
When the table output (BFM#80) is set to be stopped, the table output completion flag is turned off.
Value for each
channel
Table output completion flag
0 Table output uncompleted
1 Table output completed
Output
value
Table output start
Pattern 1
Pattern 5
Time
Change from output pattern
1 to output pattern 5
The data output in pattern 1 is
ignored, and data is output at
point 1 in output pattern 5.
H
ch4
ch3
ch2
ch1