Mitsubishi Electronics MELSEC-F Home Theater Server User Manual


 
G-7
2 Specifications
2.2 Performance Specifications
FX
3G
/FX
3U
/FX
3UC
PLC User's Manual - Analog Control Edition
FX3G-1DA-BD (1-channel analog Output)
A
Common Items
B
FX
3U
-4AD
FX
3UC
-4AD
C
FX
3U
-4AD-ADP
D
FX
3G
-2AD-BD
E
FX
3U
-4DA
F
FX
3U
-4DA-ADP
G
FX
3G
-1DA-BD
H
FX
3U
-3A-ADP
I
FX
3U
-4AD-PT
-ADP
J
FX
3U
-4AD-PTW
-ADP
2.2 Performance Specifications
Item
Specifications
Voltage output Current output
Analog output
range
0V to 10 V DC
(External load: 2kΩ to 1MΩ)
4mA to 20mA DC
(External load: 500Ω or less)
Digital input 12 bits, binary 11 bits, binary
Resolution 2.5mV(10V/4000) 8μA(16mA/2000)
Total accuracy
±0.5% (±50mV) for 10V full scale
(when ambient temperature is 25°C±5 °C)
±1.0% (±100mV) for 10V full scale
(when ambient temperature is 0°C to 55°C)
Shipment adjustment is carried out by external
load resistance 2kΩ.
If external load resistance becomes larger
than 2kΩ, the output voltage will increase
slightly.
When the load is 1MΩ, the output voltage
becomes about 2% higher than the correct
value.
±0.5% (±80μA) for 16mA full scale
(when ambient temperature is 25°C±5°C)
±1.0% (±160μA) for 16mA full scale
(when ambient temperature is 0°C to 55 °C)
D/A conversion
time
60μs (The data will be updated at every scan time.)
For a detailed description of data update, refer to Section 2.4.
Output
characteristics
Caution:
An area of dead band is located in the region
of 0V. Therefore the output analog value may
not represent the digital value accurately.
Insulation method The analog output area is not insulated from the PLC.
Numbers of I/O
points occupied
0 point (This number is not related to the maximum number of input/output points of the PLC.)
0
10V
4000 4080
Digital input
Analog output
0
2000
20mA
Digital input
Analog output
4mA
2040