Mitsubishi Electronics MELSEC-F Home Theater Server User Manual


 
E-36
5 Buffer Memory (BFM)
5.4 Buffer Memory Details
FX
3G
/FX
3U
/FX
3UC
PLC User's Manual - Analog Control Edition
FX3U-4DA (4-channel Analog Output)
5.4.20 BFM #62: Upper/lower limit function status data automatic transfer-to data register
specification
Setting range: 0 to 7999
Initial value: K201
Numeric data type: Decimal (K)
Use this function to automatically transfer the upper/lower limit function status data (BFM #39) to the data
register specified in BFM #62.
Only when the value becomes more than the upper limit or less than the lower limit, data will be automatically
transferred from FX
3U-4DA to the PLC. For this reason, the PLC does not need the program to read data, and
the scan time of the PLC can be shortened.
For a detailed description of the upper/lower limit function status (BFM #39),
refer to Subsection 5.4.14.
1. If "BFM #62 = K201 (initial value)"
2. Cautions regarding upper/lower limit function status automatic transfer function setting
If a data is already specified for the other automatic transfer functions, do not specify the same data
register.
This function is valid by turning on b1 of the status automatic transfer function setting (BFM #60).
When a value out of the above setting range is set, b9 of the error status BFM #29 is turned on.
The data set in BFM #62 will be retained in the EEPROM.
3. Cautions regarding EEPROM writing
If data is set in BFM #0, #5, #10 to #17, #19, #32 to #35, #50 to #54 or #60 to #63, the data will be written in
the EEPROM of FX
3U-4DA.
Do not turn off the power immediately after writing values in these buffer memories.
The maximum number of EEPROM rewritable times is 10,000. When creating a program, therefore, do not
frequently write data in the above buffer memories (BFM).
Specified data
register
Description
D201 Value of upper/lower limit function status (BFM #39)