Mitsubishi Electronics MELSEC-F Home Theater Server User Manual


 
E-39
6 Table Output Function
6.2 Preparation of data table
A
Common Items
B
FX
3U
-4AD
FX
3UC
-4AD
C
FX
3U
-4AD-ADP
D
FX
3G
-2AD-BD
E
FX
3U
-4DA
F
FX
3U
-4DA-ADP
G
FX
3G
-1DA-BD
H
FX
3U
-3A-ADP
I
FX
3U
-4AD-PT
-ADP
J
FX
3U
-4AD-PTW
-ADP
FX
3G
/FX
3U
/FX
3UC
PLC User's Manual - Analog Control Edition
FX3U-4DA (4-channel Analog Output)
6.2 Preparation of data table
1. Outline of data table
The data table to be prepared in the PLC consists of the following items.
(1) Number of patterns (1 to 10 patterns)
(2) Each pattern
(3) Number of points in each pattern (1 to 99 points)
(4) Condition after output at final point in each pattern
(5) Points in each pattern
(6) Data to be output at each point
(7) Output update time at each point
(8) Unit of output update time at each point, and point-to-point interpolation method
2. Preparation of data table
Prepare the data table consisting of the following items in the data registers (D1000 to D7999) in the PLC
main unit or the expansion registers (R0 to R32767).
It is convenient to prepare the data table on spreadsheet software and copy and paste the data to the device
memory of GX Developer.
Note) The device number marked by *1 should not exceed D7999 or R32767.
For a detailed description of the data table items (1) to (8), refer to the following pages.
Setting item Device number in PLC assignment
(1) Number of patterns (x) Device number specified in BFM #98
(2) Pattern 1
(3) Number of points in pattern 1 (n) Device number+1 specified in BFM #98
(4) Condition after output at final point in pattern Device number+2 specified in BFM #98
(5) Point 1
(6) Output data Device number+3 specified in BFM #98
(7) Output update time Device number+4 specified in BFM #98
(8) Unit of output update time at each point,
and point-to-point interpolation method
Device number+5 specified in BFM #98
.
.
.
.
.
.
.
.
.
(5) Point n
(6) Output data
(7) Output update time
(8) Unit of output update time at each point,
and point-to-point interpolation method
.
.
.
.
.
.
(2) Pattern X
(3) Number of points in pattern X (m)
(4) Condition after output at final point in pattern
(5) Point 1
(6) Output data
(7) Output update time
(8) Unit of output update time at each point,
and point-to-point interpolation method
.
.
.
.
.
.
.
.
.
(5) Point m
(6) Output data
(7) Output update time
(8) Unit of output update time at each point,
and point-to-point interpolation method
Device specified in BFM #98 + total number
of data tables -1
*1