E-7
2 Specifications
2.2 Power Supply Specifications
A
Common Items
B
FX
3U
-4AD
FX
3UC
-4AD
C
FX
3U
-4AD-ADP
D
FX
3G
-2AD-BD
E
FX
3U
-4DA
F
FX
3U
-4DA-ADP
G
FX
3G
-1DA-BD
H
FX
3U
-3A-ADP
I
FX
3U
-4AD-PT
-ADP
J
FX
3U
-4AD-PTW
-ADP
FX
3G
/FX
3U
/FX
3UC
PLC User's Manual - Analog Control Edition
FX3U-4DA (4-channel Analog Output)
2.2 Power Supply Specifications
2.3 Performance Specifications
*1. Adjustment of the offset or gain value will not affect the resolution. In output mode 1 or 4, however, the
offset/gain cannot be adjusted.
*2. The offset and the gain should satisfy the following condition:
1V (Gain - Offset) 10 V
*3. The offset and the gain should satisfy the following condition:
3 mA (Gain - Offset) 30 mA
Item Specifications
D/A conversion
circuit drive power
24V DC ±10%, 160mA
(It is necessary to supply 24V DC from the terminal block.)
CPU drive power
5V DC, 120mA
(Since the internal power is supplied from the main unit, it is not necessary to supply power
externally.)
Item
Specifications
Voltage output Current output
Analog output
range
-10V to +10V DC
(External load: 1kΩ to 1MΩ)
0mA to 20mA DC, 4mA to 20mA DC
(External load: 500Ω or less)
Offset
*1
-10V to +9V
*2
0mA to 17mA
*3
Gain
*1
-9V to +10V
*2
3mA to 30mA
*3
Digital input With sign, 16bits, binary 15bits, binary
Resolution 0.32mV (20V / 64,000) 0.63μA (20mA / 32,000)
Overall accuracy
Ambient temperature: 25°C±5°C
±0.3% (±60mV) for 20V full scale
Ambient temperature: 0°C to 55°C
±0.5% (±100mV) for 20V full scale
Ambient temperature: 25°C±5°C
±0.3% (±60μA) for 20mA full scale
Ambient temperature: 0°C to 55°C
±0.5% (±100μA) for 20mA full scale
Time required for
D/A conversion
1ms (The number of selected channels will not affect this value.)
Insulation method
The photocoupler is used to insulate the analog output area from the PLC.
The DC/DC converter is used to insulate the analog output area from the power supply unit.
Channels are not insulated from each other.
Number of I/O
points occupied
8 points (Taken from either the input or output points of the PLC.)