E-23
5 Buffer Memory (BFM)
5.4 Buffer Memory Details
A
Common Items
B
FX
3U
-4AD
FX
3UC
-4AD
C
FX
3U
-4AD-ADP
D
FX
3G
-2AD-BD
E
FX
3U
-4DA
F
FX
3U
-4DA-ADP
G
FX
3G
-1DA-BD
H
FX
3U
-3A-ADP
I
FX
3U
-4AD-PT
-ADP
J
FX
3U
-4AD-PTW
-ADP
FX
3G
/FX
3U
/FX
3UC
PLC User's Manual - Analog Control Edition
FX3U-4DA (4-channel Analog Output)
5.4.4 BFM #6: Output status
Initial value: H0000
Numeric data type: Hexadecimal (H)
The output status information of channel 1 to 4 is stored.
* The output conditions conform to the output setting upon PLC stop (BFM #5).
1. Cautions regarding use of output status
The output status setting is valid only if the PLC is running.
When the PLC is stopped, H0000 is automatically written.
When the setting in any of the following buffer memory areas is changed, output updating is stopped.
H0000 is automatically written in BFM #6.
BFM #0 (Output mode setting)
BFM #5 (Output setting upon PLC stop)
BFM #9 (Offset/gain setting value write command)
BFM #19 (Setting change prohibition)
BFM #20 (Initialization function)
BFM #32 to #35 (Data to be output from each channel upon PLC stop)
BFM #50 (Corrective function setting by load resistance)
BFM #51 to #54 (Load resistance for each channel)
BFM #60 (Status automatic transfer function Setting)
BFM #61 (Error status data automatic transfer-to data register specification)
BFM #62 (Upper/lower limit function status with automatic transfer to specified data register)
BFM #63 (Disconnection detection status with automatic transfer to data register specification)
BFM #99 (Data table transfer command)
Value status (HEX) Description
0 Output updating is stopped.*
1 Under output updating
H
ch4
ch3
ch2
ch1