K-6
2 Specifications
2.1 Generic Specifications
FX
3G
/FX
3U
/FX
3UC
PLC User's Manual - Analog Control Edition
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input)
2. Specifications
This chapter describes the general, power supply, and performance specifications for the PNK-ADP.
2.1 Generic Specifications
*1. The criterion is shown in IEC61131-2.
*2. If PNK-ADP is connected to the FX
3UC Series PLC, direct installation is not possible.
*3.
→ For a detailed description of the grounding, refer to Section 3.7.
*4. If the pressure is higher than the atmospheric pressure, do not use the PNK-ADP.
The PNK-ADP may malfunction.
2.2 Power Supply Specifications
Item Specifications
Ambient temperature
0 to 55°C (32 to 131°F) when operating
-25 to 75°C (-13 to 167°F) when stored
Relative humidity 5 to 95%RH (no condensation) when operating
Vibration
resistance
*1
Frequency
(Hz)
Acceleration
(m/s
2
)
Half amplitude
(mm)
Tested 10 times in
each direction (X-, Y-,
and Z-axis directions)
(Total: 80 min, each)
DIN Rail Mounting
10 - 57 - 0.035
57 - 150 4.9 -
Direct Mounting
*2
10 to 57 − 0.075
57 to 150 9.8 −
Shock resistance
*1
147 m/s
2
Acceleration, Action time: 11ms, 3 times by half-sine pulse in each direction X, Y,
and Z
Noise resistance
Using noise simulator of:
Noise voltage: 1,000Vp-p / Noise width: 1μs / Rise: 1ns / Cycle: 30 to 100Hz
Dielectric withstand
voltage
500 V AC, for 1 min
Between batch of all terminals and ground terminal
Insulation resistance
5MΩ or more using 500V DC
insulation resistance meter
Grounding
Class D grounding (grounding resistance: 100 Ω or less)
<Common grounding with a heavy electrical system is not allowed.>
*3
Working
environment
Free from corrosive or flammable gas and excessive conductive dusts
Working altitude
< 2000m
*4
Item Specifications
A/D conversion circuit
driving power
24V DC +20% -15%, 45mA
(It is necessary to connect a 24V DC power supply to the terminal block.)
Interface driving power
5V DC, 15mA
(Since the internal power is supplied from the FX Series main unit, it is not
necessary to supply the power.)
PLC
Other
equipment
PLC
Other
equipment
PLC
Other
equipment
Shared grounding
Good condition
Common grounding
Not allowed
Independent grounding
Best condition