5.4.12 BFM #29: Error status
Initial value: H0000
Numeric data type: Hexadecimal (H)
Error data is assigned to the bits of BFM #29.
2. Caution regarding error status
If the error cause is eliminated, the error bit will turn off.
Do not directly write "H0000" in BFM #29 using a sequence program.
3. Error status data automatic transfer function (b8 of BFM #22)
If the error status data automatic transfer-to data register is specified in BFM #129, the data in BFM #29 can
be transferred to the specified data register.
When an error is detected, data will be automatically transferred from 4AD to the PLC. For this reason, the
PLC does not need any program for reading the data, and the scan time of the PLC can be shortened.
: Represents a numeric value.
1. BFM #29 Bit Assignment
Bit No. Item Description
b0 Error detection If any bits between b2 and b4 are turned on, b0 will turn on.
b1 - -
b2 Power supply error
The 24 V power is not supplied properly. Check the wiring condition
or the voltage supplied.
b3 Hardware error
FX
3U-4AD/FX3UC-4AD may be defective. Please contact the nearest
Mitsubishi Electric distributor office.
b4 A/D conversion error
The A/D conversion value is abnormal.
Check the over-scale status data (BFM #28) to localize the error
channel.
b5 - -
b6
BFM reading/writing
impossible
If change in the input characteristics is started, this bit will turn on. If
this bit (b6) is on, A/D conversion data cannot be read out correctly.
b7 - -
b8 Data setting error detection If any bits between b10 and b15 are turned on, b8 will turn on.
b9 - -
b10 Averaging time setting error
The averaging time (BFM #2 to #5) is not set correctly.
Set the averaging time again in the range from 1 to 4095.
b11 Digital filter setting error
The digital filter value (BFM #6 to #9) is not set correctly.
Set the digital filter value again in the range from 0 to 1600.
b12
Abrupt change detection
value setting error
The abrupt change detection value (BFM #91 to #94) is not set
correctly.
Correctly set the value again.
b13
Upper/lower limit error
detection value setting error
The lower limit error detection value (BFM #71 to #74) or the upper
limit error detection value (BFM #81 to #84) is not set correctly.
Correctly set the value again.
b14 - -
b15 Addition data setting error
The addition data (BFM #61 to #64) is not set correctly.
Set the addition data again in the range from -16000 to +16000.
Convenient function
setting
Automatic data transfer function
ON = Valid Transfer-from memory
Transfer-to data register specification
(BFM #129: K
)
BFM #22 b8:ON BFM #29