Mitsubishi Electronics MELSEC-F Home Theater Server User Manual


 
C-22
4 Programming
4.6 Error Status
FX
3G
/FX
3U
/FX
3UC
PLC User's Manual - Analog Control Edition
FX3U-4AD-ADP (4-channel analog Input)
2. Program Example 1 (For FX3G, FX3U, FX3UC Series PLC)
*1. "1st" for the FX3G PLC.
3. Program Example 2 (For FX3U, FX3UC Series PLC)
Y000
M0
M8000
M1
M2
M3
M4
M5
M6
M7
Y001
Y002
Y003
Y004
Y005
Y006
Y007
Detects over-scale in channel 1 of
the 3rd adapter.
Detects over-scale in channel 2 of
Detects over-scale in channel 3 of
Detects over-scale in channel 4 of
EEPROM error in 3rd adapter
Averaging time setting error in
3rd adapter
Hardware error in 3rd 4AD-ADP
Communication data error in 3rd
4AD-ADP
MOV
D8288 K4M0
*1
*1
*1
*1
*1
the 3rd adapter.
*1
the 3rd adapter.
*1
the 3rd adapter.
*1
Y000
D8268.0
Y001
D8268.1
Y002
D8268.2
Y003
D8268.3
Y004
D8268.4
Y005
D8268.5
Y006
D8268.6
Y007
D8268.7
Detects over-scale in channel 1 of
the 1st adapter.
Detects over-scale in channel 2 of
the 1st adapter.
Detects over-scale in channel 3 of
the 1st adapter.
Detects over-scale in channel 4 of
the 1st adapter.
EEPROM error in 1st adapter
Averaging time setting error in
1st adapter
Hardware error in 1st 4AD-ADP
Communication data error in 1st