7 Changing Output Characteristic
7.1 Procedure for Changing Output Characteristics
A
Common Items
B
FX
3U
-4AD
FX
3UC
-4AD
C
FX
3U
-4AD-ADP
D
FX
3G
-2AD-BD
E
FX
3U
-4DA
F
FX
3U
-4DA-ADP
G
FX
3G
-1DA-BD
H
FX
3U
-3A-ADP
I
FX
3U
-4AD-PT
-ADP
J
FX
3U
-4AD-PTW
-ADP
FX
3G
/FX
3U
/FX
3UC
PLC User's Manual - Analog Control Edition
FX3U-4DA (4-channel Analog Output)
7. Changing Output Characteristic
For FX3U-4DA, the standard output characteristics are provided for each output mode (BFM #0)at the time of
factory shipment.
Changing the offset data (BFM #10 to #13) and gain data (BFM #14 to #17) can change the output
characteristics of each channel. This chapter describes how to change the output characteristics.
7.1 Procedure for Changing Output Characteristics
1 Cancel the setting change prohibition mode.
If setting change is prohibited, write K3030 in BFM #19. The setting change prohibition mode will
be canceled.
2 Determine the output mode (BFM #0).
Determine the output mode (BFM #0) optimum for the selected channels and the voltage/current
specifications.
Example: Enter "HFF00" in BFM to set output mode 0 for channels 1 and 2 and prevent use chan-
nels 3 and 4
Cautions regarding data setting
If a value "1" or "4" is set for a channel, the output characteristics of the channel cannot be changed.
Set the optimum output mode for the analog signal to be output.
Set value (HEX) Output mode Analog output range Digital input range
0 Voltage output mode -10V to +10V -32000 to +32000
1
Voltage output analog value mV
specification mode
The characteristic cannot be changed.
2 Current output mode 0mA to 20mA 0 to 32000
3 Current output mode 4mA to 20mA 0 to 32000
4
Current output analog value μA
specification mode
The characteristic cannot be changed.
5 to E Setting not allowed - -
F Channel not used - -