Mitsubishi Electronics MELSEC-F Home Theater Server User Manual


 
A-22
4 Comparison of Performance Specifications
4.1 Analog Input
FX
3G
/FX
3U
/FX
3UC
PLC User's Manual - Analog Control Edition
Common Items
4.1 Analog Input
4.1.2 FX2N-2AD
*1. For FX2N-2AD, combined use of the voltage and current inputs is not possible.
*2. Use the adjustment volume to adjust FX
2N-2AD.
*3. Adjustment of the offset or gain value will change the resolution.
Specifications
FX2N-2AD
Voltage input Current input
Number of input points 2ch
Analog input range
*1
0V to 5V DC
0V to 10V DC
(Input resistance: 200 kΩ)
4mA to 20mA DC
(Input resistance: 250Ω)
Absolute maximum input -0.5V,+15V -2mA,+60mA
Offset
If the digital value is "0":0V to 1V
*2,*3
If the digital value is "0":0mA to 4mA
*2,*3
Gain
If the digital value is "4000":
5V to 10V
*2,*3
If the digital value is "4000":20mA
*2,*3
Digital output 12 bits, binary
Resolution
2.5mV(10V×1/4000)
*3
4.00μA(16mA×1/4000)
*3
Overall accuracy
Ambient temperature:
25±5°C
--
Ambient temperature:
0 to 55°C
±1.0%(±100mV) for 10V full scale ±1.0%(±160μA) for 16mA full scale
Time required for A/D
conversion
2.5ms × number of selected channels
(Operation synchronized with sequence program)
Input characteristics
Insulation method
The photocoupler is used to insulate the analog input area from the PLC.
Channels are not insulated from each other.
Number of I/O points
occupied
8 points (Taken from either the input or output points of the PLC.)
0
4000
10V
4095
Analog input
Digital output
10.238V
4095
0
4000
20mA
Analog input
Digital input
4mA
20.380mA