8 Examples of Practical Programs
8.3 Example of Program for Table Output Operation (Pattern Output Operation)
FX
3G
/FX
3U
/FX
3UC
PLC User's Manual - Analog Control Edition
FX3U-4DA (4-channel Analog Output)
8.3 Example of Program for Table Output Operation (Pattern Output
Operation)
This section describes a practical program that uses the table output function.
1. Conditions
The sequence program described in this section is under the following conditions.
1) System configuration
FX
3U-4DA (unit No.0) should be connected to the FX3U Series PLC.
2) Output mode
Channel 1 should be set to mode 0 (voltage output, -10 V to +10 V).
Channel 3 should be set to mode 2 (current output, 0 mA to 20 mA).
Channels 2 and 4 are out of use.
3) Convenient function
The table output function is used.
4) Device assignment
* It is necessary to separately create the data table.
For a detailed description of creation of the data table, refer to Section 6.2.
2. Example of sequence program
•For FX3U, FX3UC Series PLCs
*1. The output mode setting is retained in the EEPROM of the FX
3U-4DA. For this reason, even if the
sequence program is deleted, the previously set functions will still be valid.
*2. After setting the output mode, set the data writing time (waiting time) to 5 seconds or more for each
setting. After the output mode is specified, and the same output mode is used, it is not necessary to
set the output mode and the waiting time (T0 K50).
Device Description
Input
X000 Start of table output function for channels 1 and 3
X001 Stop of table output function
X002 Restart of table output function for channel 3
D10 Data to be output from channel 1
D11 Data to be output from channel 2
D12 Data to be output from channel 3
D13 Data to be output from channel 4
D5000 or more Data table *
Output
Y000 Completion of output of table from channel 1
Y001 Table output error
M0 Data table transfer complete
M1 During output of table from channel 3
D100 Data table transfer command
D101 Table output completion flag
M8002
FNC 12
MOV
HF2F0 U0\G0
P
M8000
K50
T0
Specification of output modes of channels 1 to 4
Initial pulse
RUN monitor
*1
*2
Continued