4.4.7 FX2N-8AD
Specifications
FX2N-8AD
Centigrade(°C) Fahrenheit(°F)
Number of input points 8ch
Input signal
Thermocouple type K, J, and T
JIS C 1602-1995
Rated temperature range
Type K
-100°C to +1200°C
Type J
-100°C to +600°C
Type T
-100°C to +350°C
Type K
-148
°
F to +2192
°
F
Type J
-148
°
F to +1112
°
F
Type T
-148
°
F to +662
°
F
Digital output
Type K
-1000 to +12000
Type J
-1000 to +6000
Type T
-1000 to +3500
Type K
-1480 to +21920
Type J
-1480 to +11120
Type T
-1480 to +6620
Resolution 0.1°C
0.1
°
F
Overall accuracy
Ambient temperature:
0 to 55°C
Type K:
±0.5%(±6.5°C) for full scale
Type J:
±0.5%(±3.5°C) for full scale
Type T:
±0.7%(±3.15°C) for full scale
•Type K:
±0.5%(±11.7
°
F) for full scale
Type J:
±0.5%(±6.3
°
F) for full scale
Type T:
±0.7%(±5.67
°
F) for full scale
Time required for
conversion
40ms × number of selected channels
Input characteristics
Insulation method
The photocoupler is used to insulate the analog input area from the PLC.
The DC/DC converter is used to insulate the power supply from the analog inputs.
Channels are not insulated from each other.
Number of I/O points
occupied
8 points (Taken from either the input or output points of the PLC.)
0
+12000
(Type K)
+1200°C
(Type K)
-100°C
-1000
+600°C
(Type J)
+6000
(Type J)
+350°C
(Type T)
+3500
(Type T)
Temperature
Digital
output
0
+11120
(Type J)
+2192
°
F
(Type K)
-148
°
F
-1480
+21920
(Type K)
+1112
°
F
(Type J)
+662
°
F
(Type T)
+6620
(Type T)
Temperature
Digital
output