MDS-D/DH Series Specifications Manual
6-1 Selection of wire
6 - 7
< MDS-DH Series >
(Note) The values inside of ( ) are M side.
Terminal name
Unit type
TE1
(U,V,W, )
TE2
(L+, L-)
TE3
(L11, L21, L12, L22, MC1)
mm
2
AWG
mm
2
AWG
mm
2
AWG
Power supply
unit
MDS-DH-CV-37 214214
1.25 to 2 16 to 14
MDS-DH-CV-75 214214
MDS-DH-CV-110 2143.512
MDS-DH-CV-185 5.5 10 5.5 10
MDS-DH-CV-300 146146
MDS-DH-CV-370 146224
MDS-DH-CV-450 224303
MDS-DH-CV-550 22 4
Bar enclosed
MDS-DH-CV-750 38 2
Spindle drive
unit
MDS-DH-SP-20 214
Match with TE2 of selected
power supply unit
1.25 to 2 16 to 14
MDS-DH-SP-40 214
MDS-DH-SP-80 3.5 12
MDS-DH-SP-100 5.5 10
MDS-DH-SP-160 14 6
MDS-DH-SP-200 22 4
MDS-DH-SP-320 38 2
Bar enclosed
MDS-DH-SP-480 60 -
Servo drive
unit
MDS-DH-V1-10 214
Match with TE2 of selected
power supply unit
1.25 to 2 16 to 14
MDS-DH-V1-20 214
MDS-DH-V1-40 214
MDS-DH-V1-80 214
MDS-DH-V1-80W 214
MDS-DH-V1-160 3.5 12
MDS-DH-V1-160W 5.5 10
MDS-DH-V1-200 14 6
Servo drive
unit
(2-axis)
MDS-DH-V2-1010 214
Match with TE2 of selected
power supply unit
1.25 to 2 16 to 14
MDS-DH-V2-2010 214
MDS-DH-V2-2020 214
MDS-DH-V2-4020 214
MDS-DH-V2-4040 214
MDS-DH-V2-8040 214
MDS-DH-V2-8080 214
MDS-DH-V2-8080W 214
1. Selection conditions follow IEC/EN60204-1, UL508C, JEAC8001.
- Ambient temperature is maximum 40°C.
- Cable installed on walls without ducts or conduits.
To use the wire under conditions other than above, check the standards you are supposed to
follow.
2. The maximum wiring length to the motor is 30m.
If the wiring distance between the drive unit and motor is 20m or longer, use a thick wire so that the
cable voltage drop is 2% or less.
3. Always wire the grounding wire.
CAUTION