Mitsumi electronic IB-1500875(ENG)-E Universal Remote User Manual


 
Appendix 4 - 13
MDS-D/DH Series Specifications Manual
Appendix 4-6 EMC countermeasure parts
< 400V power line filter >
400V 3SUP-HL-ER-6B Series
Features
(a) 3-phase, 3-wire type high attenuation characteristics
(b) CE marking compatible
(c) Rated current value 30A to 200A
(d) For EN55011 Class A, B measures
(e) Application: Primary side of inverter power supply, UPS, CNC machine tool, etc.
Specifications
These specifications are for reference. Contact the filter manufacturer for detailed data.
Other matters
– If the leakage current is limited, use 3SUP-HL -ER-6B-4 (leakage current 4mA product).
– When using with the peripheral device and a higher attenuation characteristics are required, use the
3SUP-HL -ER-6.
Contact: Okaya Electric Industries Co., Ltd. Telephone: 03-3424-8120 (+81-3-3424-2110)
http://www.okayaelec.co.jp
Outline dimensions
[ Unit: mm ]
General tolerance: ± 1.5mm
Type 3SUP-HL30-ER-6B 3SUP-HL50-ER-6B 3SUP-HL75-ER-6B 3SUP-HL100-ER-6B 3SUP-HL150-ER-6B
Rated current 30A (50°C) 50A (50°C) 75A (50°C) 100A (50°C) 150A (50°C)
Maximum operation
voltage
500Vrms (50°C)
Operation frequency 50 / 60Hz
Leakage current
8mA (at 500Vrms 60Hz)
[A leakage current will not flow if there is no phase failure in a power supply grounded at a neutral point.]
Connection terminal M4 M6 M6 M6 M8
Mass 5.2kg 6.5kg 12.0kg 12.5kg 23.5kg
Nominal inductance 6 x 1.4mH 6 x 1.4mH 6 x 1.0mH 6 x 0.56mH 6 x 0.6mH
Safety standards EN133200 (compatible)
A B C D E F G H I J K L
3SUP-HL30-ER-6B 246 230 215 200 100 85 13 18 140 4.5x7 4.5 M4
3SUP-HL50-ER-6B 286 270 255 240 120 90 13 18 150 5.5x7 5.5 M6
3SUP-HL75-ER-6B 396 370 350 330 170 140 18 23 155 6.5x8 6.5 M6
3SUP-HL100-ER-6B 396 370 350 330 170 140 18 23 155 6.5x8 6.5 M6
3SUP-HL150-ER-6B 484 440 420 400 200 170 30 25 200 6.5x8 6.5 M8
3SUP-HL200-ER-6B 484 440 420 400 200 170 30 25 200 6.5x8 6.5 M8
E
+4.0/-4.0
B
D
C
+1.5/-1.5
F
H
(G)
L
L
2-
Ǿ
J
2-
ǾK
A
+1.5/ -1.5
I
Label