Mitsubishi Electronics FX2C Home Theater Server User Manual


 
FX Series Programmable Controller Diagnostic Devices 6
6-16
Error Detection
Device
Stored Error
Number
Associated Meaning Action
D8064
Parameter
error
0000 No error
STOP the PLC, select
the parameter mode, set
the correct data
6401 Pro
g
ram sum check error
6402 Memor
y
capacit
y
settin
g
error
6403 Latched device area settin
g
error
6404 Comment area settin
g
error
6405 File re
g
ister area settin
g
error
6406 - 6408 Reserved
6409 Other settin
g
error
Error Detection
Device
Stored Error
Number
Associated Meaning Action
D8065
Syntax error
0000 No error
Durin
g
pro
g
rammin
g
,
each instruction is
checked as it is entered.
If a s
y
ntax error is
detected, re-enter the
instruction correctl
y
6501
Incorrect instruction/ device s
y
mbol/
device number combination
6502
No timer or counter coil before settin
g
value
6503
1) No settin
g
value followin
g
either a
timer or a counter coil
2) Insufficient number of operands for an
applied instruction
6504
1) The same label number is used more
than once
2) The same interrupt input or hi
g
h
speed counter input is used more than
once
6505
Device number is outside the allowable
ran
g
e
6506 Invalid applied instruction
6507 Invalid P assi
g
nment
6508 Invalid I assi
g
nment
6509 Other error
6510 MC nestin
g
(N) number error
6511
Interrupt and hi
g
h speed counter
assi
g
ned inputs overlap