Mitsubishi Electronics FX2C Home Theater Server User Manual


 
FX Series Programmable Controllers Devices in Detail 4
4-17
4.9.3 Retentive Timers
A retentive timer has the abilit
y
to retain the currentl
y
reached present value even after the
drive contact has been removed. This means that when the drive contact is re-established a
retentive timer will continue from where it last reached.
Because the retentive timer is not reset when the drive contact is removed, a forced reset must
be used. The followin
g
dia
g
ram shows this in a
g
raphical format.
Using timers in interrupt or ‘CALL’ subroutines:
Please see pa
g
e 4-18.
Available devices:
Please see the information table on pa
g
e 4-15.
X0
Y0
1.23 s
t1 t2
X1
Y1
X2
t1 + t2 = 34.5s
X0
T20
T20
K123
X1
T250
K345
X2
T250RST
Y0 Y1
T250
Present value
Present value
Non-retentive timer operation