Mitsubishi Electronics FX2C Home Theater Server User Manual


 
Execution Times And Instructional Hierarchy 7
7-1
7. Execution Times And Instructional
Hierarchy
7.1 Basic Instructions
carried on over the pa
g
e......
Mnemonic
Object
Devices
Steps
Execution Time in
µ
sec
FX
0
, FX
0S
FX
0N
FX
(< Ver 3.07)
FX
(> Ver 3.07)
,
FX
2C
FX
2N(C)
ON OFF ON OFF ON OFF ON OFF ON OFF
LD
X,Y,M,S,T,C
and special M
1
3.4 3.4
0.74 0.48 0.08
LDI
AND
3.2 3.2
ANI
OR
ORI
LDP
X,Y,M,S,T,C 1 Function Not Available
43.2
LDF
ANP
37.4
ANF
ORP
ORF
ANB
Not applicable 1
2.2 2.2
0.74 0.48
0.08
ORB
MPS
2.0 2.0MRD
MPP
INV Function Not Available
MC
Nest level,
M,Y
3 17 18.2 19.2 20.4 42.8 47.8 27 30 24.8 27.5
MCR Nest level 2 6.0 6.2 40.4 19 20.8
NOP
Not applicable 1
1.6 1.6 0.74 0.48 0.08
END 410 470 960 700 508
STL
S
(see note 1)
1
4.2 + 8n 6.4 + 6.8n 39.1 + 21.1n 25 + 13.5n 27.3 + 12.6n
RET Not applicable 8.0 12.4 40.5 20 21.6
FX Series Programmable Controllers