Mitsubishi Electronics Q68RD3-G Universal Remote User Manual


 
5
UTILITY PACKAGE (GX Configurator-TI)
5.6 Monitor/Test
5.6.2 Offset/gain setting operation
5 - 23
1
OVERVIEW
2
SYSTEM
CONFIGURATION
3
SPECIFICATIONS
4
PROCEDURES AND
SETTINGS BEFORE
SYSTEM OPERATION
5
UTILITY PACKAGE
(GX CONFIGURATOR-TI)
6
PROGRAMMING
7
ONLINE MODULE
CHANGE
8
TROUBLESHOOTING
2) Setting a gain value
Enter a desired value into the Setting value field of "CH Gain setting value"
and click the button.
3) Determining the gain value
Select "Request" in the Setting value field of "CH Channel change request"
setting and click the button.
Confirm that "CH Channel change completion flag" has changed to
"Completed", and then select "OFF" in the Setting value field of "CH Channel
change request" and click the button.
Select "Invalid" in the Setting value field of "CH Gain setting channel setting"
and click the button.
(c) To set offset/gain values for more than one channel, repeat steps (a) 1) to 3) and
(b) 1) to 3).
(5) Returning to the "Monitor/test" screen
Referring to the operation described in Section 5.6.1, close the "CH Offset/gain
setting" screen and return to the "Monitor/test" screen.
(6) Writing the offset/gain setting values to the module
Write the offset/gain setting values to the module after the settings for all channels
using the user range setting have been completed. Note that if the values are written
before offset/gain setting has been completed, the status at that point will be written to
the module.
(a) How to write the values
1) Write to the Q68RD3-G
Select "Request" for "User range write request", and click .
2) Confirm the executing of writing
Confirm that the Current value field of "Offset/gain setting mode status flag"
shifts from "Offset/gain setting mode" to "Normal mode".
3) Finish writing
Select "OFF" for "User range write request", and click .
POINT
While the set data of the steps (a)1) to (a)2) above are written to the module, do
not perform the operations below. If they are performed, the data inside a flash
memory will have a problem, and the Q68RD3-G may not operate normally.
Powering off the programmable controller CPU
Resetting the programmable controller CPU
(b) Corrective action at error occurrence
Confirm that the "ERR." LED of the Q68RD3-G is off. If the "ERR." LED turns on,
click the button, check the error code on the monitor screen, and then
perform offset/gain setting again.