Mitsubishi Electronics Q68RD3-G Universal Remote User Manual


 
3
SPECIFICATIONS
3.4 Buffer Memory
3.4.23 Conversion setting for disconnection detection (Un\G164 and Un\G165)
3 - 47
1
OVERVIEW
2
SYSTEM
CONFIGURATION
3
SPECIFICATIONS
4
PROCEDURES AND
SETTINGS BEFORE
SYSTEM OPERATION
5
UTILITY PACKAGE
(GX CONFIGURATOR-TI)
6
PROGRAMMING
7
ONLINE MODULE
CHANGE
8
TROUBLESHOOTING
3.4.23 Conversion setting for disconnection detection (Un\G164 and
Un\G165)
(1) The value to be stored in the CH Measured temperature value (Un\G11
to Un\G18) when disconnection state is confirmed is selected from "Up
scale", "Down scale" or "Given value".
(2) When "Up scale"(0
H) is selected, up-scale of the currently set range is
stored in the CH Measured temperature value (Un\G11 to Un\G18).
(3) When "Down scale" (1
H) is selected, down-scale of the currently set
range is stored in the CH Measured temperature value (Un\G11 to
Un\G18).
(4) When "Given value"(2
H) is selected, the value set in the CH
Conversion setting value for disconnection detection (Un\G166 to
Un\G173) is stored in the CH Measured temperature value (Un\G11 to
Un\G18).
(5) The default value is set to "Down scale".
(6) To activate the setting, turning ON/OFF Operating condition setting
request (Y9) is required.
(7) For details, refer to Section 3.2.2.
POINT
If a value out of the setting range is set, the module operates with the default
setting, "Down scale".
0
H
1
H
2
H
b15 b12 b11 b8 b7 b4b3 b0
CH8 CH7 CH6 CH5
CH4 CH3 CH2 CH1
Un\G164 (Conversion setting for
disconnection detection CH1-4)
Un\G165 (Conversion setting for
disconnection detection CH5-8)
Measured temperature value at the
time of disconnection detection
Up scale
Down scale
Given value
Setting
value
to
to
to
to