Mitsubishi Electronics Q68RD3-G Universal Remote User Manual


 
3 - 16
3.2 Function List
3.2.3 Warning output function
3
SPECIFICATIONS
2) Setting example of the rate alarm upper/lower limit values for monitoring that a
measured temperature value decreases within the specified range
3) Setting example of the rate alarm upper/lower limit values for monitoring that a
measured temperature value changes within the specified range
(f) When disconnection state is detected, the measured temperature value is
replaced with the setting in the Conversion setting for disconnection detection
(Un\G164 and Un\G165), such as "Down scale". As a result, a warning may occur.
(g) After connection is restored, preceding values required for rate alarm occurrence
are cleared.
Therefore, a warning does not occur even though the changed portion of
measured temperature values before and after temperature conversion exceeds
the setting range when temperature conversion is restarted.
Change of
measured
temperature
value ( C)
Rate alarm upper limit value
Rate alarm lower limit value
Time
0
-10.0
C
-20.0
C
Change of
measured
temperature
value ( C)
0
-10.0
C
10.0
C
Rate alarm upper limit value
Rate alarm lower limit value
Time