3.4 Buffer Memory
3.4.13 Warning output flag (Process alarm/Rate alarm) (Un\G47 and Un\G48)
3
SPECIFICATIONS
3.4.13 Warning output flag (Process alarm/Rate alarm) (Un\G47 and
Un\G48)
(1) When a measured temperature value is out of the setting range of the
CH Process alarm upper/lower limit values (Un\G94 to Un\G125) or
CH Rate alarm upper/lower limit values (Un\G134 to Un\G149), the bit
of the corresponding channel turns ON (changes to "1").
(2) For both process alarm and rate alarm, whether the warning is for the
upper limit value or lower limit value can be checked for each channel.
(3) When the measured temperature value or the change of measured
temperature values returns to within the setting range, this flag will be
automatically reset.
(4) If a warning is detected on any of channels for which conversion and
warning output of process alarm or rate alarm are enabled, Warning
output signal (XD) also turns ON.
(5) When Operating condition setting request (Y9) is turned ON, this flag
will be cleared.
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
Un\G47 (Process alarm)
Un\G48 (Rate alarm)
0: Normal
1: Alarm ON
0: Normal
1: Alarm ON
CH7 upper
limit value
CH8 lower
limit value
CH7 lower
limit value
CH8 upper
limit value
CH6 upper
limit value
CH6 lower
limit value
CH4 upper
limit value
CH5 lower
limit value
CH4 lower
limit value
CH5 upper
limit value
CH3 upper
limit value
CH3 lower
limit value
CH2 upper
limit value
CH2 lower
limit value
CH1 upper
limit value
CH1 lower
limit value
CH7 upper
limit value
CH8 lower
limit value
CH7 lower
limit value
CH8 upper
limit value
CH6 upper
limit value
CH6 lower
limit value
CH4 upper
limit value
CH5 lower
limit value
CH4 lower
limit value
CH5 upper
limit value
CH3 upper
limit value
CH3 lower
limit value
CH2 upper
limit value
CH2 lower
limit value
CH1 upper
limit value
CH1 lower
limit value