6 - 27
6.3 Using Programs on Remote I/O Network
6.3.3 Program example when utility package is not used
6
PROGRAMMING
* 2 Un\G24: Averaging processing selection (CH1-CH4) (Refer to Section 3.4.9.)
* 3 Un\G46: Warning output enable/disable setting (Refer to Section 3.4.12.)
* 4 D1024 and D1046 are used for writing the initial setting data. (D2024 and D2046 are used for
reading the initial setting data.)
(3) GX Developer operation (Network parameter setting)
• Refresh parameters:
• Network type : MNET/H [Remote master]
• Starting I/O No. : 0000
H
• Network No. : 1
• Total stations : 1
• Mode : Online
• Network range assignment :
H
0420
0
H
(Sampling processing)
2
H
(Count average)
4
H
(Primary delay filter)
CH4 CH3 CH2 CH1
H
FBFD
10111111
Rate alarm setting
b7 b6 b5 b4 b3 b2 b1 b0
CH8CH7CH6CH5 CH4CH3CH2CH1
CH3: 0 (Enable)
CH1, CH2, CH4 to CH8: 1 (Disable)
11011111
Process alarm setting
b7 b6 b5 b4 b3 b2 b1 b0
CH8CH7CH6CH5 CH4CH3CH2CH1
CH2: 0 (Enable)
CH1, CH3 to CH8: 1 (Disable)