7 - 10
7.3 Procedures of Online Module Change
7.3.2 When factory default is used and initial setting has been made with sequence program
7
ONLINE MODULE CHANGE
(b) Click the button to enable a module change.
If the following screen appears, click the button, remove the module,
and mount a new module.
(c) After confirming that the "RUN" LED of the module has turned off, disconnect the
connector and remove the module.
POINT
Make sure to remove the module. If the mounting status is confirmed ("Installation
confirmation" is executed) without removing the module, the module will not start
properly and the "RUN" LED will not turn on.
(3) Mounting a new module
(a) Mount a new module to the same slot and connect the connector.
(b) After mounting the module, click the button and confirm that the "RUN"
LED is on. Module ready (X0) remains OFF.