3.4 Buffer Memory
3.4.24 CH[] Conversion setting value for disconnection detection (Un\G166 to Un\G173)
3
SPECIFICATIONS
3.4.24 CH[] Conversion setting value for disconnection detection
(Un\G166 to Un\G173)
(1) When "Given value" (2H) is set in the Conversion setting for
disconnection detection (Un\G164 and Un\G165), the value set in this
area is stored in the CH Measured temperature value (Un\G11 to
Un\G18) at the time of disconnection detection.
When "Up scale" (0
H) or "Down scale" (1H) is set in the Conversion
setting for disconnection detection, the settings in these area take no
effect.
(2) Setting range is from -32768 to 32767 (0000
H to FFFFH) (in units of 0.1 ).
[Example]
When setting the value to 0.3 Store "3" in the buffer memory.
(3) The default value is set to "0".
(4) To activate the setting, turning ON/OFF Operating condition setting
request (Y9) is required.