3 - 30
3.4 Buffer Memory
3.4.2 Conversion enable/disable setting (Un\G0)
3
SPECIFICATIONS
3.4.2 Conversion enable/disable setting (Un\G0)
(1) Temperature conversion enable/disable status is set for each channel.
(2) Setting "Disable" for unused channels can prevent unnecessary
disconnection detection.
(3) The default value is set to "Disable" for all channels.
[Example]
(4) To activate the setting, turning ON/OFF Operating condition setting
request (Y9) is required.
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
CH8 CH7 CH6 CH5 CH4 CH3 CH2 CH100000000
Data for b8 to b15 are fixed to "0".
0: Enable
1: Disable
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
1111110000000000
Channel 1 and 2 are enabled for conversion.