7.4 Range Reference Table
7
ONLINE MODULE CHANGE
(Example)
When offset/gain setting is performed, setting the offset setting temperature at
-200.0 and the gain setting temperature at 850.0 , with a Pt100 platinum RTD
connected
Table 7.4 How to obtain reference value
Value type
Setting
temperature
Reference value of User range
settings resistance offset/gain
values
Reference value of User range settings offset/gain values
Offset value
-200.0
18520 ( 10
-3
)
Gain value
850.0
390480 ( 10
-3
)
(18520 100000)
15052
197160
7643 1422 058EH
(390480 100000)
15052
197160
7643 29819 747BH