6 - 9
6.2 Using Programs in Normal System Configuration
6.2.2 Program example when utility package is used
6
PROGRAMMING
(2) Utility package operation
(a) Initial setting (Refer to Section 5.4.)
Set the items shaded in the table below to CH1 to CH3.
Setting for the items with " " is not required when "Disable", "Invalid" or "Down
scale" has been selected.
(Default value, which will be displayed in the Setting value field, does not need to
be changed.)
* 1 The setting is used to switch the process alarm setting value input range. Use the same range set
for the measurement range setting at the intelligent function module switch 1 and 2. (In this
program example, "New JIS (-200 to 850 )" is set.)
Table 6.3 List of initial setting items
Setting item Default CH1 CH2 CH3
Conversion enable/disable
setting
Disable
Enable Enable Enable
Averaging processing selection Sampling Sampling Count Primary delay filter
Time/Count/Moving average/
Time constant setting
0
0 5 960
Process alarm warning output
enable/disable setting
Disable
Disable Enable Disable
Setting range
New JIS
(-200 to 850 )
Setting not required
(Default value)
New JIS
(-200 to 850 )
*1
Setting not required
(Default value)
Process alarm lower lower limit
value
-2000
2000
Process alarm lower upper limit
value
-2000
2050
Process alarm upper lower limit
value
8500
2950
Process alarm upper upper limit
value
8500
3000
Rate alarm warning output
enable/disable setting
Disable
Disable Disable Enable
Rate alarm warning detection
period
1
Setting not required
(Default value)
Setting not required
(Default value)
3
Rate alarm upper limit value 0 50
Rate alarm lower limit value 0 -50
Scaling valid/invalid setting Invalid Invalid Invalid Invalid
Scaling range lower limit value 0
Setting not required
(Default value)
Setting not required
(Default value)
Setting not required
(Default value)
Scaling range upper limit value 0
Scaling width lower limit value 0
Scaling width upper limit value 0
Conversion setting for
disconnection detection
Down scale
Down scale Down scale Down scale
Conversion setting value for
disconnection detection
0