6 - 5
6.2 Using Programs in Normal System Configuration
6
PROGRAMMING
(3) Programming conditions
(a) Use the following temperature conversion system for each channel.
CH1: Sampling processing
CH2: Count average (5 times)
CH3: Primary delay filter (Time constant 960ms)
(b) Use the following function at each channel.
CH2: Warning output function
CH3: Warning output function
(c) Use the following setting for the Conversion setting for disconnection detection of
CH1 to CH3.
CH1 to CH3: Down scale (-252.5 ) [Default setting]
(d) When a write error occurs, the corresponding error code is output to an output
module in BCD value.
Process alarm lower lower limit value: 2000 (200 ),
Process alarm lower upper limit value: 2050 (205 ),
Process alarm upper lower limit value: 2950 (295 ),
Process alarm upper upper limit value: 3000 (300 )
Rate alarm warning detection period: 3 times (960ms),
Rate alarm lower limit value: -50 (-5.0 ),
Rate alarm upper limit value: 50 (+5.0 )