Mitsubishi Electronics Q68RD3-G Universal Remote User Manual


 
7
ONLINE MODULE CHANGE
7.3 Procedures of Online Module Change
7.3.3 When user range setting is used and initial setting has been made with GX Configurator-TI (Separate
7 - 15
1
OVERVIEW
2
SYSTEM
CONFIGURATION
3
SPECIFICATIONS
4
PROCEDURES AND
SETTINGS BEFORE
SYSTEM OPERATION
5
UTILITY PACKAGE
(GX CONFIGURATOR-TI)
6
PROGRAMMING
7
ONLINE MODULE
CHANGE
8
TROUBLESHOOTING
(3) Mounting a new module
(a) Mount the removed module and a new module to a separate system.
(b) Using the G(P).OGLOAD instruction, save the user range setting values to the
CPU device. For the G(P).OGLOAD instruction, refer to Appendix 1.3.
(c) Using the G(P).OGSTOR instruction, restore the user range setting values to the
module. For the G(P).OGSTOR instruction, refer to Appendix 1.4.
(d) Remove the new module from the separate system, mount it to the slot from
where the old module was removed in the original system, and connect the
connector.
(e) After mounting the module, click the button and confirm that the "RUN"
LED is on. Module ready (X0) remains OFF.
(4) Checking operation
(a) For checking operation, click the button to cancel the restart of control
to the module.