3 - 12
3.2 Function List
3.2.3 Warning output function
3
SPECIFICATIONS
(c) Settable temperature range and default value vary according to the RTD type to
be used and measurement range.
Values are set in units of 0.1 .
(d) When time average or count average is specified, process alarm processing is
executed for each preset time or count.
When other temperature conversion system (sampling processing, moving
average or primary delay filter) is specified, process alarm processing is executed
at every sampling period.
(e) When disconnection state is detected, the measured temperature value is
replaced with the setting in the Conversion setting for disconnection detection
(Un\G164 and Un\G165), such as "Down scale". As a result, a warning may occur.
Table 3.7 Settable range and default value of process alarm
RTD type
Measurement
range
Default value
Settable temperature
range
(Accuracy guarantee
range)
(in units of 0.1 )
Process alarm
lower upper limit
value
(in units of 0.1 )
Process alarm
lower lower limit
value
(in units of 0.1 )
Process alarm
upper upper limit
value
(in units of 0.1 )
Process alarm
upper lower limit
value
(in units of 0.1 )
Pt100
(New JIS)
-200 to 850
-2000 8500 -2000 to 8500
-20 to 120
-200 1200 -200 to 1200
0 to 200
0 2000 0 to 2000
JPt100
(Old JIS)
-180 to 600
-1800 6000 -1800 to 6000
-20 to 120
-200 1200 -200 to 1200
0 to 200
0 2000 0 to 2000
Ni100
-60 to 180
-600 1800 -600 to 1800