Mitsubishi Electronics Q68RD3-G Universal Remote User Manual


 
4
PROCEDURES AND SETTINGS BEFORE SYSTEM
OPERATION
4.6 Offset/Gain Setting
4 - 10
1
OVERVIEW
2
SYSTEM
CONFIGURATION
3
SPECIFICATIONS
4
PROCEDURES AND
SETTINGS BEFORE
SYSTEM OPERATION
5
UTILITY PACKAGE
(GX CONFIGURATOR-TI)
6
PROGRAMMING
7
ONLINE MODULE
CHANGE
8
TROUBLESHOOTING
4.6 Offset/Gain Setting
Set offset/gain setting values in the following procedure.
When factory default settings are used, offset/gain setting is not required.
If the utility package is installed, set offset/gain setting values according to the procedure
described in Section 5.6.2.
(1) Setting procedure
Identify the disconnected
channel with the
Disconnection detection flag
(Un\G49), review the wiring
of the corresponding
channel, and turn YF from
ON to OFF.
YES
NO
1)
1)
2)
Input a value used as a gain value to the
adjusting target channel using a RTD or
standard resistor.
Check that the "RUN" LED is flashing to indicate
the offset/gain setting mode.
Switch to the offset/gain setting mode.
*1
Confirm that the Channel change completion flag
(XB) has turned ON.
Set the gain setting channel in the Offset/gain
setting mode (Gain specification) (Un\G27) and set
"0" in the Offset/gain setting mode (Offset
specification) (Un\G26).
Confirm that the Offset/gain setting mode status flag
(XA) has turned OFF.
Write the measurement setting value equivalent to
the input to the CH Gain temperature setting
value (Un\G29)
*3
of the adjusting target channel.
Set the offset setting channel in the Offset/gain
setting mode (Offset specification) (Un\G26) and
set "0" in the Offset/gain setting mode (Gain
specification) (Un\G27).
Set "Enable" for the Conversion enable/disable
setting (Un\G0) of the offset/gain setting target
channel and turn Y9 from ON to OFF.
*2
With the intelligent function module switch
setting, set the RTD type to be used and the
temperature range for the measurement range
setting of a channel targeted for adjusting
offset/gain values.
Confirm that the Channel change completion
flag (XB) has turned ON.
Input a value used as an offset value to the
adjusting target channel using a RTD or
standard resistor.
Turn OFF Channel change request (YB).
Turn ON Channel change request (YB).
Turn ON Channel change request (YB).
Turn OFF Channel change request (YB).
Turn ON User range write request (YA).
Turn OFF User range write request (YA).
Switch to the normal mode.
Start
Adjust other channels?
Is Disconnection detection
signal (XC) ON?
YES
NO
YES
NO
2)
Is the "ERR." LED on?
End
Write the measurement setting value equivalent
to the input to the CH Offset temperature
setting value (Un\G28)
*3
of the adjusting target
channel.
*4