Mitsubishi Electronics Q68RD3-G Universal Remote User Manual


 
3 - 6
3.2 Function List
3.2.1 Temperature conversion system
3
SPECIFICATIONS
(c) Moving average
Measured temperature values, which are measured every sampling period for the
specified number of times, are averaged and the averaged value is stored in the
buffer memory.
The latest measured temperature value can be obtained since averaging
processing is performed moving for each sampling period.
Moving average processing with 4-time setting
Measured
temperature value
Sampling period (320ms)
1st storage
2nd storage
3rd storage
Buffer memory
Measured
temperature value
Conversion completion flag turns ON (changes to "1").
Time [ms]
Data transition in buffer memory
1st storage
2nd storage
3rd storage
444
16000
8000
0
1)
2)
3)
4)
5)
6)
7)
8)
9)
10)
11)
12)
1)+2)+3)+4) 2)+3)+4)+5) 3)+4)+5)+6)