3.4 Buffer Memory
3.4.6 Error code (Un\G19)
3
SPECIFICATIONS
3.4.6 Error code (Un\G19)
(1) Error code that is detected by the Q68RD3-G is stored.
(2) For details on error codes, refer to Section 8.1.
3.4.7 Setting range 1, 2 (Un\G20 and Un\G21)
(1) This area is for checking the measurement range of the Q68RD3-G,
which is set with Switch 1 and 2 in the intelligent function module switch
setting.
Setting values of the measurement range are stored into the area
indicated below for each channel.
(2) The following table shows the measurement range and setting value for
each RTD.
3.4.8 Setting range 3 (Offset/gain setting) (Un\G22)
(1) This area is for checking the offset/gain setting of the Q68RD3-G, which
is set with Switch 3 in the intelligent function module switch setting.
"0" is stored for factory default setting and "1" is stored for user range
setting.
Table 3.11 Measurement range and setting value
RTD Measurement range Setting value
Pt100
-200 to 850
0
H
-20 to 120
1
H
0 to 200
4
H
JPt100
-180 to 600
2
H
-20 to 120
3
H
0 to 200
5
H
Ni100
-60 to 180
8
H
b0
Un\G20
(Setting range 1 CH1-4)
Un\G21
(Setting range 2 CH5-8)
b15
b12 b11
b8 b7
b4b3
CH4 CH3 CH1
CH8 CH7 CH6 CH5
CH2
to
to
to
to
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
CH8 CH7 CH6 CH5 CH4 CH3 CH2 CH100000000
Data for b8 to b15 are fixed to "0".
0: Factory default setting
1: User range setting