3 - 10
3.2 Function List
3.2.2 Conversion setting for disconnection detection function
3
SPECIFICATIONS
(6) It takes 640ms (maximum) to obtain normal measured temperature
values after connection is restored.
Temperature conversion restarts 640ms after connection is restored.
When averaging processing is set, it takes another 640ms and time
required for averaging processing before normal measured temperture
values are stored to the CH Measured temperature value (Un\G11 to
Un\G18) after the restart of temperature conversion. During the time
before normal measured temperature values are stored in the buffer
memory, the measured temperature values remain the value specified in
the The Conversion setting for disconnection detection (Un\G164 and
Un\G165), such as "Down scale".
(7) For operation of the warning output function when disconnection is
detected or recovered, refer to Section 3.2.3.