4.5 Intelligent Function Module Switch Setting
4
PROCEDURES AND SETTINGS BEFORE SYSTEM
OPERATION
(2) Operating procedure
Make settings on the I/O assignment tab of PLC parameter in GX Developer.
(a) I/O assignment tab
Set the following for the slot in which the Q68RD3-G is mounted.
The "Type" setting is mandatory, but other items are optional. Set them as
needed.
Type : Select "Intelli.".
Model name : Enter the module model name.
Points : Select "16points".
StartXY : Enter the start I/O number of the Q68RD3-G.
Detailed setting: Specify the control programmable controller of the Q68RD3-G.
It is unnecessary to set the "Error time output mode" and "H/W error time PLC
operation mode" since these settings are invalid for the Q68RD3-G.
(b) Switch setting for intelligent function module screen
Click the button on the I/O assignment tab to display the screen shown
below, then make settings for Switch 1 to 5.
The switches can be set easily if values are entered in hexadecimal. Change the
"Input format" to "HEX." (hexadecimal) and then enter setting values.