7 - 18
7.3 Procedures of Online Module Change
7.3.4 When user range setting is used and initial setting has been made with GX Configurator-TI (Separate
7
ONLINE MODULE CHANGE
7.3.4 When user range setting is used and initial setting has been made
with GX Configurator-TI (Separate system is not available)
(1) Disabling conversion
(a) Set "Disable" in the Setting value field of "Conversion enable/disable setting" on
the "CH Monitor/test" screen in GX Configurator-TI, and click the
button.
(b) Confirm that the Current value field of "Conversion enable/eisable setting" has
been changed to "Disable", and then select "Request" in the Setting value field of
"Operation condition setting request" on the "Monitor/test" screen and click the
button to stop conversion.
Monitor the Conversion completion flag (Un\G10) and confirm that conversion has
stopped.