Mitsubishi Electronics Q68RD3-G Universal Remote User Manual


 
7 - 32
7.3 Procedures of Online Module Change
7.3.6 When user range setting is used and initial setting has been made with sequence program (Separate
7
ONLINE MODULE CHANGE
(4) Checking operation
(a) For checking operation, click the button to cancel the restart of control
to the module.
(b) Click the button to leave the "Online module change" mode.
(c) Click the button to close the "System monitor" screen.
(d) Set the noted values to the buffer memory on the screen displayed by selecting
[Online] - [Debug] - [Device test] in GX Developer.
(e) Turn User range write request (YA) from OFF to ON to restore the user range
setting values to the module.
After confirming that Offset/gain setting mode status flag (XA) is ON, turn OFF
User range write request (YA).