4 - 10
CHAPTER4 ASSIGNMENT OF BASE UNIT AND I/O NUMBER
1
2
3
4
5
6
7
8
4.2 I/O Number Assignment
4.2.2 Setting I/O numbers
(b) Type
Select the type of the mounted module from the followings:
• Empty (empty slot)
• Input (input module)
• Hi input (high-speed input module)
• Output (output module)
• I/O Mix (I/O combined module)
• Intelli. (intelligent function module)
• Interrupt (interrupt module)
If the type is not specified, the type of the actually mounted module is used.
(c) Type
Enter the model names of mounted modules within 16 characters.
CPU modules do not use entered model names. (Use the entered model names for user reference.)
(d) Points
When changing the number of I/O points for each slot, the selections are as follows.
0 points, 16 points, 32 points, 48 points, 64 points, 128 points, 256 points, 512 points, 1024 points
If the number of points is not selected, the points of the actually mounted module is used.
For empty slots, the points that are set on the PLC system tab of the PLC parameter dialog box is assigned.
(Default: 16 points)
(e) Start XY
When changing the I/O number for each slot, enter a new start I/O number.
If start XY is not specified for a slot, the I/O number continuing from the last number of the current
setting is assigned.