Mitsubishi Electronics QnUCPU Home Theater Server User Manual


 
8 - 18
*1: Not available for the Q00UCPU, Q01UCPU, and Q02UCPU.
*2: SM, SD, SB, and SW are valid only when they are selected as send devices.
Table8.13 Multiple CPU setting list (continued)
Item
Parameter
No.
Description Setting range Default Reference
Online module change
*1
E006H
Enable or disable the online
module change in the multiple
CPU system. (When enabled,
the CPU module cannot read
the I/O data outside the
specified group.)
Selected/deselected Deselected
QQCPU Userís
Manual (Multiple
CPU System)
I/O sharing when
using Multiple CPUs
All CPUs
can read all
inputs
0E04
H
Select whether to read the
input data of the input modules
or intelligent function modules
controlled by another CPU.
Selected/deselected Deselected
All CPUs
can read all
outputs
Select whether to read the
output data of the output
modules controlled by another
CPU.
Selected/deselected Deselected
Multiple
CPU high
speed
transmiss
ion area
setting
*1
CPU specific send
range
E008
H
Set the size of the multiple
CPU high-speed transmission
area that is assigned to each
CPU module of the multiple
CPU system.
Simple setting:
0 to 12K (in increments of 1K
points)
Advanced setting:
0 to 16K (in increments of
0.5K points)
3K points
Auto
refresh
setting
Refresh
setting
E009
H
E00AH
Set an area range for data
communication performed with
the auto refresh function in the
user area of the multiple CPU
high-speed transmission area.
Available devices
*2
:
X, Y, M, L, B, D, W, R, ZR,
SM, SD, SB, and SW
-
Communication area setting
(refresh setting)
E002
H
E003H
In the multiple CPU system,
data are transferred by auto
refresh among respective CPU
modules.
Set the devices to be written or
read and their points.
[Set starting devices for each
CPU]
Selected/deselected
Deselected
[CPU specific send range]
0 to 2048 points (in
increments of 2 points) per
CPU
Up to 8K points (8192 points)
per system
Blank
[PLC side device]
B, M, Y, D, W, R, or ZR
Occupies the device of the
points set for the send range
and starting from the
specified device number.
One point in the send
range equals 16 points in
B, M, or Y.
One point in the send
range equals one point in
D, W, R, or ZR.