12.1 SPECIAL RELAY LIST
*1: This applies to the CPU of function version B or later.
*2: The module whose first 5 digits of serial No. is "09012" or later.
*5: The Universal model QCPU except the Q00UJCPU, Q00UCPU, Q01UCPU, and Q02UCPU.
*6: The module whose first 5 digits of serial No. is "10042" or later.
*8: The Universal model QCPU except the Q00UJCPU.
Table12.3 Special relay
Number Name Meaning Explanation
Set by
(When Set)
Corres-
ponding
ACPU
M9
Corresponding
CPU
SM240 No. 1 CPU reset flag
OFF : No. 1 CPU reset
cancel
ON : No. 1 CPU resetting
Goes OFF when reset of the No. 1 CPU is canceled.
Comes ON when the No. 1 CPU is resetting
(including the case where the CPU module is
removed from the base).
The other CPUs are also put in reset status.
S (Status change) New
Q00/Q01
*1
Qn(H)
*1
QnPH
QnU
*8
SM241 No. 2 CPU reset flag
OFF : No. 2 CPU reset
cancel
ON : No. 2 CPU resetting
Goes OFF when reset of the No. 2 CPU is canceled.
Comes ON when the No. 2 CPU is resetting
(including the case where the CPU module is
removed from the base).
The other CPUs result in "MULTI CPU DOWN" (error
code: 7000).
SM242 No. 3 CPU reset flag
OFF : No. 3 CPU reset
cancel
ON : No. 3 CPU resetting
Goes OFF when reset of the No. 3 CPU is canceled.
Comes ON when the No. 3 CPU is resetting
(including the case where the CPU module is
removed from the base).
The other CPUs result in "MULTI CPU DOWN" (error
code: 7000).
SM243 No. 4 CPU reset flag
OFF : No. 4 CPU reset
cancel
ON : No. 4 CPU resetting
Goes OFF when reset of the No. 4 CPU is canceled.
Comes ON when the No. 4 CPU is resetting
(including the case where the CPU module is
removed from the base).
The other CPUs result in "MULTI CPU DOWN" (error
code: 7000).
Qn(H)
*1
QnPH
QnU
*5
SM244 No. 1 CPU error flag
OFF : No. 1 CPU normal
ON : No. 1 CPU during stop
error
Goes OFF when the No. 1 CPU is normal (including
a continuation error).
Comes ON when the No. 1 CPU is during a stop
error.
Q00/Q01
*1
Qn(H)
*1
QnPH
QnU
*8
SM245 No. 2 CPU error flag
OFF : No. 2 CPU normal
ON : No. 2 CPU during stop
error
Goes OFF when the No. 2 CPU is normal (including
a continuation error).
Comes ON when the No. 2 CPU is during a stop
error.
SM246 No. 3 CPU error flag
OFF : No. 3 CPU normal
ON : No. 3 CPU during stop
error
Goes OFF when the No. 3 CPU is normal (including
a continuation error).
Comes ON when the No. 3 CPU is during a stop
error.
SM247 No. 4 CPU error flag
OFF : No. 4 CPU normal
ON : No. 4 CPU during stop
error
Goes OFF when the No. 4 CPU is normal (including
a continuation error).
Comes ON when the No. 4 CPU is during a stop
error
S (Status change) New
Qn(H)
*1
QnPH
QnU
*5
SM250 Max. loaded I/O read
OFF : Ignored
ON : Read
When this relay goes from OFF to ON, maximum
loaded I/O number is read to SD250.
UNew
Qn(H)
QnPH
QnPRH
SM254
All stations refresh
command
OFF : Refresh arrival station
ON : Refresh all stations
Effective for the batch refresh (also effective for the
low speed cyclic)
Designate whether to receive arrival stations only or
to receive all slave stations in the MELSECNET/H.
UNew
Designate whether to receive arrival stations only or
to receive all slave stations in the CC-Link IE
controller network .
Qn(H)*
2
QnPH*
6
QnPRH*
6
Effective for the batch refresh (also effective for the
low speed cyclic)
Specify whether to receive only arrival station or all
stations in the MELSECNET/H or CC-Link IE
controller network.
QnU