Mitsubishi Electronics QnUCPU Home Theater Server User Manual


 
12 - 36
Table12.18 Special register
Number Name Meaning Explanation
Set by
(When Set)
Corres-
ponding
ACPU
D9
Corresponding
CPU
SD50 Error reset
Error number that
performs error
reset
Stores error number that performs error reset U New
QCPU
SD51
Battery low
latch
Bit pattern
indicating where
battery voltage
drop occurred
All corresponding bits go 1(ON) when battery voltage drops.
Subsequently, these remain 1(ON) even after battery voltage has been
returned to normal.
In the alarm, data can be held within the time specified for battery low.
The error indicates the complete discharge of the battery.
S (Error) New
SD52 Battery low
Bit pattern
indicating where
battery voltage
drop occurred
Same configuration as SD51 above
After the alarm is detected (ON), the alarm turns OFF by error detection
(ON). (For the Universal model QCPU only)
Turns to 0 (OFF) when the battery voltage returns to normal thereafter.
S (Error) New
SD53
AC/DC DOWN
detection
Number of times
for AC/DC DOWN
detection
Every time the input voltage falls to or below 85% (AC power)/65% (DC
power) of the rating during operation of the CPU module, the value is
incremented by 1 and stored in BIN code.
The counter repeats increment and decrement of the value ;
0 32767 -32768 0
S (Error) D9005
SD60
Number of
module with
blown fuse
Number of module
with blown fuse
Value stored here is the lowest station I/O number of the module with
the blown fuse.
S (Error) D9000
SD61
I/O module
verify error
number
I/O module verify
error module
number
The lowest I/O number of the module where the I/O module verification
number took place.
S (Error) D9002
0
b3 b2 b1 b0
CPU error
1: This
does not app
ly
to Bas
ic
model QCPU.
alarm
error
b15
to
1