6 - 50
(4) Operating instructions
(a) Registering executional conditioned device test settings
Select the registration target step number on the program editing screen in GX Developer. Then, select
[Online] [Debug] [Executional conditioned device test] [Register executional conditioned device test].
*1: When a word device which is index-modified or indirectly-specified is set, only "16 bit integer" can be specified.
1) Multiple executional conditioned device test registrations for the same step
number
Multiple executional conditioned device test settings can be registered for one step number.
However, if multiple executional conditioned device test settings with same device name and same execution
timing are registered for the same step number, the registration data will be overwritten. (Even though the
same device is specified, if the execution timing differs, two settings can be registered for one step.)
Figure 6.41 Screen for registering executional conditioned device test settings
Table6.16 Items on the screen for registering executional conditioned device test settings
No. Item
Setting range
For bit device For word device
1) Program name Name of a program registered in the CPU module
2) Step No. 0 to (Step number for the END instruction)
3) Device Device listed in (2) in this section
4) Execution timing Before executing instruction / After executing instruction
5) Setting value - (Not specified) Setting range corresponding to each data type
6) DEC / HEX - (Not specified) DEC (decimal) / HEX (hexadecimal)
7)
Data type
*1
- (Not specified)
16 bit integer / 32 bit integer / Real number (single
precision) / Real number (Double precision)
3)
5)
1)
2)
4)
6)
7)
Devices that executional conditioned device test settings
can be registered for the start step of the + instruction.
+ D0 D10 D20