(10)Batch transfer of data to the program memory
When data in the program cache memory is batch-transferred to the program memory by GX Devel-
oper, the processing time shown in Table10.28 is required.
*1
*1: The time in the table is for the case where the service processing count is set to one.
(11) Diagnostics of the redundant power supply system
When the "Diagnose redundant power supply system." is selected on the PLC RAS tab of the PLC
parameter dialog box, the processing time shown in
Table10.29 is required.
*1: A power supply module failure indicates any of the following.
The redundant power supply module has failed.
Power for the redundant power supply module is turned off.
The redundant power supply module is not mounted.
Table10.28 Processing time (when data is batch-transferred to the program memory)
CPU module
Processing time
Scan time = 2ms Scan time = 20ms
Q00UJCPU, Q00UCPU, Q01UCPU 1.90ms 4.90ms
Q02UCPU 1.55ms 4.50ms
Q03UDCPU, Q03UDECPU 1.10ms 3.65ms
Q04UDHCPU, Q06UDHCPU, Q10UDHCPU, Q13UDHCPU,
Q20UDHCPU, Q26UDHCPU, Q04UDEHCPU, Q06UDEHCPU,
Q10UDEHCPU, Q13UDEHCPU, Q20UDEHCPU, Q26UDEHCPU
1.05ms 3.65ms
Table10.29 Processing time (when the diagnostics for the redundant power supply system is enabled)
CPU module
Processing time
With a power supply module
failure
*1
Without a power supply module
failure
*1
Q00UCPU
125
s 165 s
Q01UCPU
125
s 135 s
Q02UCPU
90
s 90 s
Q03UDCPU, Q04UDHCPU, Q06UDHCPU, Q10UDHCPU,
Q13UDHCPU, Q20UDHCPU, Q26UDHCPU, Q03UDECPU,
Q04UDEHCPU, Q06UDEHCPU, Q10UDEHCPU, Q13UDEHCPU,
Q20UDEHCPU, Q26UDEHCPU
43