Mitsubishi Electronics QnUCPU Home Theater Server User Manual


 
12 - 6
*1: This applies to the CPU of function version B or later.
Table12.3 Special relay
Number Name Meaning Explanation
Set by
(When Set)
Corres-
ponding
ACPU
M9
Corresponding
CPU
SM255
MELSECNET/10,
MELSECNET/H
module 1 information
OFF : Operative network
ON : Standby network
Goes ON for standby network(If no designation has
been made concerning active or standby, active is
assumed.)
S (Initial) New
Qn(H)
QnPH
QnPRH
SM256
OFF : Reads
ON : Does not read
For refresh from link to CPU module (B, W, etc.)
indicate whether to read from the link module.
UNew
SM257
OFF : Writes
ON : Does not write
For refresh from CPU module to link (B, W, etc.),
designate whether to write to the link module.
UNew
SM260
MELSECNET/10,
MELSECNET/H
module 2 information
OFF : Operative network
ON : Standby network
Goes ON for standby network
(If no designation has been made concerning active
or standby, active is assumed.)
S (Initial) New
SM261
OFF : Reads
ON : Does not read
For refresh from link to CPU module (B, W, etc.)
indicate whether to read from the link module.
UNew
SM262
OFF : Writes
ON : Does not write
For refresh from CPU module to link (B, W, etc.),
designate whether to write to the link module.
UNew
SM265
MELSECNET/10,
MELSECNET/H
module 3 information
OFF : Operative network
ON : Standby network
Goes ON for standby network
(If no designation has been made concerning active
or standby, active is assumed.)
S (Initial) New
SM266
OFF : Reads
ON : Does not read
For refresh from link to CPU module (B, W, etc.)
indicate whether to read from the link module.
UNew
SM267
OFF : Writes
ON : Does not write
For refresh from CPU module to link (B, W, etc.),
designate whether to write to the link module.
UNew
SM270
MELSECNET/10,
MELSECNET/H
module 4 information
OFF : Operative network
ON : Standby network
Goes ON for standby network
(If no designation has been made concerning active
or standby, active is assumed.)
S (Initial) New
SM271
OFF : Reads
ON : Does not read
For refresh from link to CPU module (B, W, etc.)
indicate whether to read from the link module.
UNew
SM272
OFF : Writes
ON : Does not write
For refresh from CPU module to link (B, W, etc.),
designate whether to write to the link module.
UNew
SM280 CC-Link error
OFF : Normal
ON : Error
Goes ON when a CC-Link error is detected in any of
the installed CC-Link module. Goes OFF when
normal operation is restored.
S (Status change) New
SM315
Communication
reserved time delay
enable/disable flag
OFF : Without delay
ON : With delay
This flag is enabled when the time reserved for
communication processing is set in SD315.
Turns ON to delay the END processing by the time
set in SD315 in order to perform communication
processing.
(The scan time increases by the period set in
SD315.)
Turns OFF to perform the END processing without a
delay of the time set in SD315 when there is no
communication processing. (Defaults to OFF)
U New Q00J/Q00/Q01
SM320
Presence/absence of
SFC program
OFF : SFC program absent
ON : SFC program present
Turns ON when an SFC program is registered.
OFF when an SFC program is not registered.
S (Initial) M9100
Q00J/Q00/Q01
*1
Qn(H)
QnPH
QnPRH
QnU
SM321
Start/stop SFC
program
OFF : SFC program not
executed (stop)
ON : SFC program executed
(start)
Initial value is set at the same value as SM320.
(Goes ON automatically if SFC program is present.)
Turn this relay from ON to OFF to stop program
execution.
Turn this relay from OFF to ON to resume program
execution.
S (Initial)/U
M9101form