Mitsubishi Electronics QnUCPU Home Theater Server User Manual


 
CHAPTER6 FUNCTIONS
1
2
3
4
5
6
7
8
6.11 Monitor Function
6.11.4 Executional conditioned device test
6 - 49
(2) Available devices and number of settable devices
*1: The extended data register (D) is included.
*2: The extended link register (W) is included.
(3) How to check the execution status
The execution status of registered executional conditioned device test can be checked in three different ways:
By the flash of the MODE LED in green
By the on status of the first bit of SD840 (Debug function usage)
By the display on the screen for checking the registration status in GX Developer
( (4)(d) in this section)
The MODE LED also flashes in green when the external input/output forced on/off function is used.
To check the execution status using the MODE LED, check the status of the external input/output forced on/off function
as well. ( Section 6.11.3)
When using SD840 to check the execution status, remind that SD840 is used to check the status of the external input/
output forced on/off function as well.
Table6.15 Available devices and number of settable devices
Type Available device
Number of settable
devices
Bit device
X, Y, M, L, B, F, SB, V, SM, T (contact), ST (contact), C (contact), J \X, J \Y,
J \B, J \SB, FX, FY, DX, and DY
Up to 32 (in total)
Word device
T (current value), ST (current value), C (current value), D
*1
, SD, W
*2
, SW, R,
ZR, Z, U \G , U3E \G , J \W , J \SW , and FD
Digit-specified bit device:
X, Y, M, L, F, SM, V, B, SB, J \X, J \Y, J \B, and J \SB
Indirect specification (@D0): D, SD, W, SW, R, and ZR (devices specified with
@)