8 - 3
CHAPTER8 PARAMETERS
1
2
3
4
5
6
7
8
8.1 PLC Parameters
(2) PLC system
Parameters required for use of the CPU module are set.
(To the next page)
Figure 8.2 PLC system
Table8.2 PLC system setting list
Item
Parameter
No.
Description Setting range Default Reference
Timer limit
setting
Low speed
1000
H
Set the time limit for the low
speed timer or high speed timer.
1ms to 1000ms (in increments of 1ms) 100ms Section 9.2.10
High speed
0.01ms to 100.0ms (in increments of
0.01ms)
10.0ms Section 9.2.10
RUN-
PAUSE
contcts
RUN
1001H
Set the contacts that control RUN/
PAUSE of the CPU module.
Setting of only the PAUSE contact
is not allowed.
X0 to 1FFF Blank
Section 6.6.1
PAUSE Section 6.6.2
Latch data backup
operation valid contact
1014
H
Set the valid contact device No.
for backup of latch data to the
standard ROM.
X, M, B Blank Section 6.28
Remote reset 1002
H
Select whether to allow the
remote reset from GX Developer.
Selected/deselected Deselected Section 6.6.3
Output mode at STOP to
RUN
1003
H
Set the status of the outputs (Y)
when the operating status is
switched from STOP to RUN.
Previous state, Recalculate (output is 1
scan later)
Previous state Section 6.4
Intelligent function module
setting (Interrupt pointer
setting)
100A
H
Assign the interrupt pointers (I50
to I255) and set the start I/O
number and start SI number of
each intelligent function module.
• Start I/O No.
•Start SI No.
• I50 to 255
Blank Section 9.11
Module synchronization 100C
H
Select whether to synchronize
CPU module startup with
intelligent function module
startup.
Selected/deselected Deselected -