6.24 Service Processing
6.24.1 Service processing setting
6 - 129
(2) Parameter setting
Set the parameters in the PLC system tab of the PLC parameter dialog box.
To perform the service processing, select any of the parameter items in Table6.43.
The setting value of deselected parameter cannot be entered (default: Execute the process as the scan time
proceeds. = 10%).
Figure 6.95 Parameter setting screen
Table6.43 Parameter items
Item Description Setting range Remarks
Execute the process as
the scan time proceeds.
Set the percentage of service processing
for one scan.
• Range: 1 to 99%
• Unit: 1%
Default when selected =10%
Specify service process
time.
Set the time of service processing for one
scan.
• Range: 0.2ms to 1000ms
• Unit: 0.1ms
Default when selected =0.2ms
Specify service process
execution counts.
Set the number of service processing for
one scan.
• Range: 1 to 10 times
• Unit: 1 time
Default when selected
=1 time
Execute it while waiting
for constant scan setting.
Set whether to perform service
processing during waiting time for
constant scan setting.
-
Even when the waiting time is
0.2ms or less, the service
processing time (0.2ms) will be
added to the scan time at service
processing execution.