(6) Device
Number of points, latch range, and local device range are set for each device.
(To the next page)
Figure 8.6 Device
Table8.6 Device setting list
Item
Parameter
No.
Description Setting range Default Reference
Device points
*1
2000H
Set the number of device points
that is appropriate to the system.
X (8K), Y (8K), and S (8K)
*3
are fixed.
Setting is available within the range of
29K words in total, including the above
fixed points (1.5K words).
One device: Up to 32K points
Total bit device points: Up to 64K
points
•X: 8K
•Y: 8K
•M: 8K
•L: 8K
*2
•B: 8K
•F: 2K
•SB: 2K
•V: 2K
•S: 8K
*3
•T: 2K
•ST: 0K
•C: 1K
•D: 12K
•W: 8K
•SW: 2K
Section 9.1
Latch (1) start/end (Latch
clear valid)
*2
2001H
Set a latch range (start and end
device numbers), which can be
cleared by remote latch clear
operation.
Setting is available for only one range
for each of B, F, V, T, ST, C, D, and W
devices.
Blank Section 3.4, 6.3
Latch (2) start/end (Latch
clear invalid)
*2
2002H
Set a latch range (start and end
device numbers), which cannot be
cleared by remote latch clear
operation.
Setting is available for only one range
for each of L, B, F, V, T, ST, C, D, and W
devices.
Blank Section 3.4, 6.3
Local device start/end
*6
2003H
Set a range (start and end device
numbers), which is used for a
local device.
Setting is available for only one range
for each of M, V, T, ST, C, D, and Z
devices.
*5