Mitsubishi Electronics QnUCPU Home Theater Server User Manual


 
6 - 102
: Self-diagnostics is performed. : Self-diagnostics is not performed
(To the next page)
Table6.29 Self-diagnostics list (continued)
Diagnostics
Error message Diagnostic timing
CPU
module
status
LED status
Q00UJ
CPU
Q00U
CPU,
Q01U
CPU
Q02U
CPU
QnUD(H)
CPU
Built-in
Ethernet
port
QCPU
RUN ERR.
SFC parameter error
SFC
PARA.ERROR
Switching from
STOP to RUN
Writing to
programmable
controller
Stop
Off
Flashi
ng
Intelligent function module
parameter error
SP.PARA.
ERROR
• Power-on/reset Stop
Off
Flashi
ng
Password error
REMOTE
PASS.ERR
• Power-on/reset
Switching from
STOP to RU
Stop
Off
Flashi
ng
Instruction code check
INSTRUCT.
CODE ERR
• Power-on/reset
Switching from
STOP to RUN
• Execution of an
instruction
Stop
Off
Flashi
ng
No END instruction
MISSING END
INS.
• Power-on/reset
Switching from
STOP to RUN
Stop
Off
Flashi
ng
Pointer setting error
CANëT SET(P)
• Power-on/reset
Switching from
STOP to RUN
Stop
Off
Flashi
ng
CANëT SET(I)
• Power-on/reset
Switching from
STOP to RUN
Stop
Off
Flashi
ng
Program
error
Operation
error
*1 *4
OPERATION
ERROR
• Execution of an
instruction
Stop/
continue
Off/on
Flashi
ng/on
FOR to NEXT
instructions
structure error
FOR NEXT
ERROR
• Execution of an
instruction
Stop
Off
Flashi
ng
CALL to RET
instructions
structure error
CANëT
EXECUTE(P)
• Execution of an
instruction
Stop
Off
Flashi
ng
Interrupt
program error
CANëT
EXECUTE(I)
• Execution of an
instruction
Stop
Off
Flashi
ng
Instruction
execution
disabled
INST. FORMAT
ERR.
• Execution of an
instruction
Stop
Off
Flashi
ng
Dedicated
instruction of
multiple CPU high
speed bus error
MULTI
COM.ERROR
• Execution of an
instruction
Stop
Off
Flashi
ng
SFC block
configuration
error
CANëT
SET(BL)
Switching from
STOP to RUN
Stop
Off
Flashi
ng
SFC step
configuration
error
CANëT SET(S)
Switching from
STOP to RUN
Stop
Off
Flashi
ng
SFC execution
error
SFC EXE.
ERROR
Switching from
STOP to RUN
Stop
Off
Flashi
ng